Safety Protection Measures And Requirements For Safe Use Of Wires And Cables

1. When the cables are inserted into each other, the high-voltage wires shall be under the high-voltage cables. If one of the cables passes through the pipe for maintenance or is separated by a partition within 1m before and after the insertion point, the minimum allowable interval is 0.25m.

2. When the cable is close to or interpenetrated with the heat pipe, if there are thermal insulation measures, the minimum interval between parallel and interpenetration is 0.5m and 0.25m.

3. When the cable crosses the railway or road, it shall be maintained through the pipe, and the maintenance pipe shall extend 2m away from the road or road surface.

4. The distance between the cable and the foundation of the building shall ensure that the cable is buried outside the apron of the building; When the cable is led into the building, it shall be maintained through the pipe, and the maintenance pipe shall also be beyond the apron of the building.

5. The distance between the cable indirectly buried underground and the grounding of ordinary grounding installation shall be 0.25 ~ 0.5m; The buried depth of cables indirectly buried underground shall not be less than 0.7m and shall be buried under the frozen soil layer.